Power and water move a delivery date, not the hardware. Check these against your hall early, and send them with your first message.

The envelope

Reference values

A B300 node draws roughly 14 kW. Four of them in a rack is 56 kW, which one 100 kW CDU carries with headroom to spare. The figures below are the reference envelope for a liquid cooled rack. Check them against your hall early, because power and water are what move a delivery date, not the hardware.

A rack holding four nodes and a switch, connected through a manifold to a coolant distribution unit by supply and return lines. SWITCH DGX B300 10U / 14 KW DGX B300 10U / 14 KW DGX B300 10U / 14 KW DGX B300 10U / 14 KW SUPPLY / 0 TO 123 LPM RETURN CDU 100 KW
Rack loop, four nodes to one CDU
Facility
Ambient air temperature
Below 35 °C
Relative humidity
Below 85%
Rack size
750 x 1200 mm
Allowable rack weight
Above 1000 kg
Coolant loop
Fluid type
Water
Supply flow rate
0 to 123 LPM
Supply temperature
2 °C to 45 °C
Pump head, CDU pressure drop
0 to 200 kPa
Cooling capacity
100 kW per CDU
Supply route
Through raised floor
Filtration
Strainer, below 300 µm
Loop hardware
Facility water connectors
1.25 in cam-lock, male and female
Shutoff ball valves
Supply and return
Circuit setter
Return side
Bypass, drain valves, expansion tank
Present
Water quality
Standard
ASHRAE, purified water
pH
6.5 to 8
Conductivity at 20 °C
Below 10 µS/cm
Turbidity
Below 1 NTU
Metals
Below 0.1 ppm
Chloride, nitrate, nitrite, sulfate
Below 0.5 ppm each
Bacteria
Below 100 cfu/mL

Reference envelope for a liquid cooled rack. Your binding figures come from the integration partner's site survey and govern over anything shown here.